30 FLA 3 Pole Definite Purpose Contactor
Technical Parameters
3 Pole | Coil Voltage 50/60Hz | Full Load Amps | Line Voltage | Locked Rotor Amps | Resistive Amps Rating | Maximum Horsepower | Single Phase | Three Phase | Approx. Unit Weight |
---|---|---|---|---|---|---|---|---|---|
20 FLA | 24 110/120 208/240 277 |
20 | 240/277 480 600 |
120 100 80 |
30 30 30 |
110/120 200/240 480/600 |
1.5 - |
- 7.5 7.5 |
0.1 lb 0.45 kg |
25 FLA | 24 110/120 208/240 277 |
25 | 240/277 480 600 |
150 125 100 |
35 35 35 |
110/120 200/208 240/277 480 600 |
2 - 5 - |
0.75 - 10 15 20 |
0.1 lb 0.45 kg |
30 FLA | 24 110/120 208/240 277 |
30 | 240/277 480 600 |
180 150 120 |
40 40 40 |
110/120 200/208 240/277 480 600 |
2 - 5 - |
- 10 15 20 |
0.1 lb 0.46 kg |
COIL TECHNICAL DATA 50/60HZ
Name | 24V | 120V | 208/240V | 277V | 480V |
---|---|---|---|---|---|
Nominal Coil Voltage | 24 | 120 | 208/240 | 277 | 480 |
Maximum Pickup Volts | 18 | 88 | 177 | 220 | 384 |
Drop-Out Volts Range | 6-15 | 20-70 | 40-140 | 65-165 | 150-270 |
Nominal Inrush VA @50HZ | 65 | 65 | 65 | 65 | 65 |
Nominal Inrush VA @60HZ | 60 | 60 | 60 | 60 | 60 |
Nominal Sealed VA @50HZ | 7.5 | 7.5 | 7.5 | 7.5 | 7.5 |
Nominal Sealed VA @60Hz | 6 | 6 | 6 | 6 | 6 |
Nominal DC Resistance (Ω) | 6.6 | 165 | 660 | 880 | 1320 |
Maximum Coil Voltage | 30 | 132 | 264 | 300 | 528 |