WTM7-63 4P DC Miniature Circuit Breaker MCB

Rated voltage: 1000 V DC with four poles in series, the highest DC rating in the WTM7-63 frame and the version used on 1000 V DC combiners and storage racks.

Pole configuration: Four poles tied to one handle in a 72 mm body, 18 mm per pole, so a single movement opens every pole.

Current ratings: 6, 10, 16, 20, 25, 32, 40, 50 and 63 A on the C curve, with the thermal magnetic trip inside a standard moulded case.

Polarity marking: Plus and minus are printed on the terminal blocks and the front diagram shows the pole pairs wired in series, so a reversed DC feed is visible before the first cable goes in.

Terminals: 25 mm² copper at 2.5 Nm, IP20 front, DIN rail mounting, incoming feed from the top or the bottom.

WTM7-63 4P DC Miniature Circuit Breaker for 1000 V DC Distribution

The 4P version of the WTM7-63 frame carries 1000 V DC by putting four poles in series, so it protects the DC side of a 1000 V array, a battery rack or a DC combiner box with one DIN rail device. Four poles share one handle, and the terminals carry plus and minus marks from the factory.

Four poles for 1000 V DC

Each pole is rated for 250 V DC. Wired in series, the four poles hold 1000 V DC, which is the top of the frame and twice the working voltage of the 2P version. The front wiring diagram shows the pole pairs and their series links, so an installer can follow it terminal by terminal.

One handle, all four poles

The poles are tied to a single linkage, so a fault on any one pole opens the whole device and the operator cannot leave half a DC circuit live. Manual isolation follows the same movement, which matters when a string has to be made safe for service.

Ratings and curve

Nine ratings run from 6 A to 63 A, all C curve. The thermal element carries 1.13 In continuously and trips at 1.45 In inside the hour, while the magnetic element picks up near 10 In for short circuit faults on cables and combiner hardware.

Arc control in direct current

A direct current arc does not stop at a zero crossing, so the arc chamber, the contact gap and the series arrangement of the poles carry the duty. Splitting 1000 V DC across four breaks keeps the arc energy at each gap at a level the moulded case was built to handle.

Breaking capacity, width and wiring

Ultimate breaking capacity is 6 kA with the service capacity at 100 percent, insulation voltage 1000 V and impulse withstand 6 kV. The body is 72 mm wide on 35 mm DIN rail, terminals take 25 mm² copper at 2.5 Nm, the front is IP20, and the feed may come from the top or the bottom.

Tell us the DC voltage, the pole count your panel drawing calls for and the current rating, and we will confirm the exact WTM7-63 order code and delivery time.

CONTACT US

Start Your Electrical Project Today

Send your application, voltage, certifications and quantity to this electrical protection manufacturer. We reply with a quotation within 24 hours.
  • Engineering review by an electrical protection manufacturer before quoting
  • Plant pricing with no intermediaries
  • Export packing and shipping handled in one place
  • One order owner from quotation to delivery