CJX2K-06 AC Contactor 6A IEC/UL
The CJX2K-06 is the smallest frame in the CJX2K range, rated 6A in AC-3 duty at 380V. It is built for control panels that switch small motors, fans and auxiliary circuits and keep a 16A thermal rating in reserve.
Current and Voltage
Rated operational current is 6A AC-3 at 380V and 5A at 660V, on an agreed heating current of 16A. Rated working voltage covers 380V and 660V, with 690V rated insulation voltage.
Coil and Control Circuit
Coils are available for AC 12V, 24V, 48V, 110V, 220V and 380V. Pull-in takes 0.85 to 1.1 times the rated control voltage and release happens between 0.2 and 0.75 times, so the contactor drops out on a genuine undervoltage. Inrush power is 40VA, holding power 4VA, dissipation 1.2W, pull-in time 6 to 18ms and release time 5 to 12ms.
Life and Auxiliary Contact
Electrical life is 500,000 operations in AC-3 duty at up to 1200 per hour, and 100,000 operations in AC-4 duty at 300 per hour. Mechanical life is 10 million. The auxiliary contact carries 5A conventional thermal current with 500,000 electrical operations at AC.
Where the 6A Frame Fits
Use the CJX2K-06 where the motor rating sits at or below 6A AC-3 and the panel needs a compact three pole device with a 690V insulation rating. Tell us the motor rating, coil voltage and auxiliary contact count and we will confirm the model.