CJX2-8011 AC Contactor 80A for 37kW Motor Starting
At 80A the CJX2-8011 is built for 37kW three-phase motors at 380/400V and for the cable sizes that come with them. Three main poles carry the load, and the NO plus NC auxiliary pair handles control and status signals.
Current Ratings
AC-3 rating is 80A at 380/400V and 49A at 660/690V, with a 95A thermal frame. AC-4 rating is 37A at 380V and 17.3A at 660V, which leaves margin for plugging duty on compressors and crushers.
Auxiliary and Control
The auxiliary contacts are rated 10A thermal at AC-15 380V and DC-13 220V, with 360VA AC-15 control capacity. Motor ratings are 22kW at 220V, 37kW at 380/400V and 45kW at 660V.
Coil Loading
Coil voltages run AC 36V, 110V, 127V, 220V and 380V. Closing power is 200VA, holding power 20VA and coil loss 6W to 10W, with pick-up at 85% to 110% Us and drop-out between 20% and 75% Us.
Life Expectancy and Parts
Electrical life is 600,000 operations at AC-3 and 100,000 at AC-4, mechanical life 6 million, at up to 600 operations per hour. Wiring capacity is 25mm², matching RT16-100 fuses and JR28-93 thermal relays. Send the motor rating and coil voltage and we will confirm the model.