30 FLA 2 Pole Definite Purpose Contactor
Two pole version of the 30 FLA contactor, the usual choice for single phase condensing units and fan circuits where both lines are switched. Each pole carries 30 FLA with 150A locked rotor at 240/277V.
Contact Rating Per Pole
The per pole rating is 30 FLA, 150A LRA and 40A resistive at 240/277V. At 480V the pole carries 30 FLA and 125A LRA, at 600V 30 FLA and 100A LRA, with the 40A resistive rating unchanged across the range.
Coil and Control
A 208-240VAC 50/60Hz coil is fitted as standard, and 24, 120 and 480VAC coils are available in the same frame. The moving contact bridge drives both poles from that single coil.
Terminals and Mounting
Main terminals are 10-32 screws, and box lug terminations are offered on the larger 40 FLA and above frames. The base uses the NEMA mounting pattern and NO or NC end switch kits can be added for fan and compressor sequencing.
Life and Ambient Range
Life rating is 100,000 or 250,000 cycles depending on version, with an operating range of -40 to +150 degrees F, or -40 to +65 degrees C. Tell us the FLA, coil voltage and pole count and we will confirm the model.