30 FLA 1 Pole Definite Purpose Contactor
The single pole version of the 30 FLA frame, used where only one line of a single phase circuit has to be broken. It carries 30 FLA and 150A locked rotor at 240/277V, with a 40A resistive rating for heating circuits.
Contact Rating Per Pole
At 240/277V the pole is rated 30 FLA, 150A LRA and 40A resistive. At 480V it is 30 FLA, 125A LRA and 40A resistive, and at 600V 30 FLA, 100A LRA and 40A resistive.
Coil and Control
The coil is 208-240VAC 50/60Hz as standard, with 24, 120 and 480VAC options in the same frame. No end switch is fitted unless ordered, and NO or NC end switch kits are available.
Terminals and Mounting
Main terminals are 10-32 screws, matching the wire size used on 30 FLA control circuits. The base follows the NEMA mounting pattern, so the single pole unit shares the bracket layout of the multi pole versions.
Life and Ambient Range
Life rating is 100,000 or 250,000 cycles depending on the version, and the contactor operates from -40 degrees F to +150 degrees F, or -40 to +65 degrees C. Tell us the FLA, coil voltage and enclosure needs and we will confirm the model.