CJX2-F115 High Ampere AC Contactor 115A
The CJX2-F115 is the entry size of the F series, the frame that takes over from the CJX2-D range at 115A. It holds 200A conventional thermal current and 55kW motor rating at 380/400V, with NT1 fuses as the matching short circuit protection.
Current Data
Rated operational current is 115A in AC-3 duty at 380/400V and 86A at 660/690V. Conventional thermal current in AC-1 duty is 200A, which is the figure to use when the contactor switches resistive or lightly inductive loads.
Motor Capacity
For three-phase cage motors the frame is rated 55kW at 380/400V and 80kW at 660/690V. That covers 55kW pumps, compressors and fans on 400V networks and the equivalent load on 690V systems.
Life and Duty
Electrical life reaches 1.2 million operations at AC-3, mechanical life 10 million, and the frame allows 1200 operations per hour. This is the point where the F series sits above the smaller CJX2 frames in both current and endurance.
Terminals and Protection
Main pole terminals use M6 screws, sized for the cable lugs fitted on 115A feeders. The matched fuse is an NT1 link rated 250A. Tell us the motor rating, coil voltage and pole count you need and we will confirm the model.