CJX2D95 New Type Magnetic AC Contactor 95A
The CJX2D95 is a Magnetic Contactor 95A rated model and the largest frame in the CJX2D range, carrying 95A in AC-3 duty on a 125A thermal frame. Insulation and rated operating voltage reach 1000V, and the terminal layout follows LC1D practice.
Power Range
Motor power is 25kW at 220/230V, 45kW at 380/400V and 415/440V, 55kW at 500V and 45kW at 660/690V. This covers 45kW motors on mains panels and larger pumps in 690V networks.
Heavy Duty
Inching and plugging duty is rated 9kW at 220/230V, 15kW at 380/400V and 415/440V, 22kW at 500V and 25kW at 660/690V.
Coil and Auxiliary
Coil inrush is 200VA and holding power 20VA, with pick-up at 85% to 110% Us and drop-out between 20% and 75% Us. One NO and one NC auxiliary contact are rated 10A at AC-15 360VA and DC-13 33W.
Service Life
Electrical life is 600,000 operations at AC-3 and 100,000 at AC-4, mechanical life 4 million, at up to 750 operations per hour. Tell us the motor rating and coil voltage and we will confirm the model.