CJ19 Contactor Capacitor Switching 115A
CJ19 Contactor for Capacitor Switching 115A.
Request A Quote
WTAIELE builds AC and DC contactors from 6 A to 410 A for motor control, capacitor switching and DIN-rail boards, at our plant in Liushi, Yueqing.
Start with what the contactor has to switch, not with the model number. A three-phase induction motor on an AC supply takes a CJX2 frame sized on AC-3 current. A battery, solar string or 48 V DC bus takes a CJX2-Z frame, because the arc needs magnetic blowout that an AC frame does not have. Where the neutral has to break with the phases, or two single-phase circuits run through one device, it takes a four-pole frame.
Two smaller ranges cover the rest: CJ19 for capacitor banks, where the inrush is far above the rated current, and WTH8 for DIN-rail boards in apartments and small commercial panels.
Whichever range you open, the order needs three things: the frame current, the coil voltage of the control circuit, and the auxiliary contacts the panel logic uses.
CJ19 Contactor for Capacitor Switching 115A.
CJ19 Contactor for Capacitor Switching 170A.
MC-40a Magnetic Contactor 40A, 220V AC coil, 18.5kW at 380/400V, 1NO+1NC auxiliary contacts, DIN rail or screw fixing.
MC-85a Magnetic Contactor 85A, 220V AC coil, 45kW at 380/400V, 2NO+2NC auxiliary contacts, DIN rail or screw fixing.
WTH8-63 household modular contactor 63A, 63 thermal current, DIN rail mounting, coil operated, 36mm wide 2 pole body.
WTH8-40M manual household modular contactor 40A, manual lever plus coil, 63 thermal current, 15 AC-7a at 400V, 35mm DIN rail.
WTH8-40 household modular contactor 40A, 63 thermal current, DIN rail mounting, coil operated, 36mm wide 2 pole body.
WTH8-16 household modular contactor 16A, 25 thermal current, DIN rail mounting, coil operated, 18mm wide 2 pole body.
WTH8-16M manual household modular contactor 16A, manual lever plus coil, 25 thermal current, 6 AC-7a at 400V, 35mm DIN rail.
Send the motor rating, the supply voltage and the coil voltage on the panel. We reply within 24 hours with the frame, coil code and auxiliary block, and confirm the stock position for the quantity.