WXU-07 Phase Asymmetry Relay with Delay

Asymmetry dial: The Asy knob sets the unbalance threshold from 5% to 15% between the three phases.

Delay: Tt holds the action back for 0.1 to 10 seconds, so a short imbalance during a motor start does not trip the circuit.

Fixed voltage setting: The unit is supplied for the line voltage of the order, and the two positions used by voltage knobs on the sibling models are blanked off.

Output: One changeover contact on 11-12-14, 10A thermal current and 250V 2.5A under AC-15, with a 500mW minimum load.

Panel: One 18mm module on a 35mm rail, insulation 500V and impulse withstand 2.5kV, with a supply lamp and a red output lamp.

WXU-07 Phase Asymmetry Relay with Adjustable Delay

The WXU-07 does one job: it watches how evenly the load sits across the three phases and drops its contact when the spread passes the limit set on the face. It suits a panel where the voltage itself is already supervised upstream and the missing piece is a check on balance.

Two Dials, Two Jobs

The upper dial sets the asymmetry threshold from 5% to 15% and the lower one sets the action delay from 0.1 to 10 seconds. The two positions that carry voltage threshold knobs on the sibling models are blanked off on this one, so there is no voltage threshold to set and nothing to read wrong.

Asymmetry Rather Than Absolute Voltage

A supply can sit comfortably inside its voltage window and still be badly out of balance, and that is the condition that heats a stator winding fastest. Reading the spread between phases catches a loose terminal, a single blown capacitor in a bank, or a load that has been added to one phase of a three phase board. An open phase is detected at 70% of the rated voltage alongside the balance check.

Delay and Reset

The delay keeps the contact in while a large motor starts and drags the phases apart for a moment, which is where a fast asymmetry relay earns its nuisance trips. Power on delay is 0.5 seconds and reset time is 1 second, so the relay settles after a supply break instead of latching a fault. Measurement covers 45Hz to 65Hz with an error of 1% or less.

Output and Panel Fit

The output is a changeover contact on 11, 12 and 14 rated 10A thermal current and 250V 2.5A under AC-15, with a 500mW minimum switching power. Rated insulation voltage is 500V and impulse withstand 2.5kV, mechanical life 10 million operations against 100,000 electrical. The face carries a supply lamp and a red output lamp, and the body carries CE and CCC marking. One 18mm module fits a 35mm rail. Send your unbalance limit, line voltage and quantity to WTAIELE for a quote.

CONTACT US

Start Your Electrical Project Today

Send your application, voltage, certifications and quantity to this electrical protection manufacturer. We reply with a quotation within 24 hours.
  • Engineering review by an electrical protection manufacturer before quoting
  • Plant pricing with no intermediaries
  • Export packing and shipping handled in one place
  • One order owner from quotation to delivery